تخطي للذهاب إلى المحتوى

RELAY SCHNEIDER FLAT 14 PIN 24VDC 6A

(مراجعة 0 )
RXM4AB1BD
اشترِ الآن
السعر
6.49 6.49 (غير شامل الضريبة)

Terms and Conditions
15-days money-back guarantee

RXM miniature relays are part of Harmony Electromechanical Relays. This is a plug in relay to be mounted on a RXZE socket. It is a 4 C/O relay with current rating of 6A, control circuit voltage of 48 V AC 50/60 Hz. It also offers one-step loackable test button and mechanical indicator for contact status. The testbutton is activated momentarily by pushing the red pushbutton on the front and locked by flipping up the green part. The mechanical indicator is next to the testbutton, where an orange flag indicates the relay contact status. A green LED on the front will illuminate when the relay is on. Status display with LED: clearly signal both in the day and night. Its design is fit for industrial machines, packaging, textile, HVAC, automation control panels, low/medium voltage switchgear, motor controls, PLC Interfaces, power supplies, building or medical equipment, lighting controls. It conforms to international standards and certifications like IEC, CE, UL, CSA, EAC, Lloyd's, RoHS and REACH. RXM Relay should be used with a RXZE socket (screw clamp, screw connector, push-in terminal). To protect against vibrations, plastic/metal clamp can be added to the socket. Protection modules and marking legend are also available. It is sold in lots of 10 and reference includes relay only. The RXM plug-in relays are a series of industrial plug-in relays designed for both simple and complex automation systems and available with 2 CO (12A), 3 CO (10A), 4 CO (6A) contacts, 4 CO (3A) low level contacts.

Main
Range of Product
Harmony Electromechanical Relays
Series name
RXM series
Product or Component Type
Plug-in relay
Relay Type
Miniature relay
Contacts type and composition
4 C/O
Status LED
With
Control Type
Lockable test button
[Uc] control circuit voltage
48 V AC 50/60 Hz
[Ithe] conventional enclosed 
thermal current
6 A
Continuous output current                                      
5 A
Complementary
[Uimp] rated impulse withstand voltage
2.5 kV 1.2/50 µs
[Ie] rated operational current
3 A 28 V DC) NC IEC
3 A 250 V AC) NC IEC
6 A 28 V DC) NO IEC
6 A 250 V AC) NO IEC
6 A 277 V AC) UL
8 A 30 V DC) UL
Minimum switching capacity
170 mW 10 mA, 17 V
Electrical durability
100000 cycles resistive
Average coil consumption in VA
1.2 60 Hz
Rated operational voltage limits
38.4...52.8 V AC
[Ui] rated insulation voltage
250 V IEC
300 V CSA
300 V UL
Average consumption
1.2 VA 60 Hz
Maximum switching voltage
250 V IEC
Drop-out voltage threshold
>= 0.15 Uc
Load current
6 A 250 V AC
6 A 28 V DC
Operating time
20 ms
Maximum switching capacity
1500 VA/168 W
Average resistance
710 Ohm 20 °C +/- 15 %
Mechanical durability
10000000 cycles
Safety reliability data
B10d = 100000
Operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Utilisation coefficient
20 %
CAD overall height
3.3 in (82.8 mm)
CAD overall depth
3.16 in (80.35 mm)
reset time
20 ms
Dielectric strength
1300 V AC between contacts with micro disconnection
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
Compatibility code
RXM
Protection category
RT I
Pollution degree
2
Operating position
Any position
Test levels
Level A group mounting
Device presentation
Complete product
Contacts material
AgNi
Shape of pin
Flat (faston type)
Net Weight
0.082 lb(US) (0.037 kg)
Environment
Ambient air temperature 
for operation                                                                     
-40…131 °F (-40…55 °C)
IP degree of protection
IP40 conforming to IEC 60529
Standards
CSA C22.2 No 14
UL 508
IEC 61810-1
Product Certifications
UL
Lloyd's
CE
CSA
GOST
IECEE CB Scheme
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Vibration resistance
3 gn +/- 1 mm 10…150 Hz)5 cycles in operation
5 gn +/- 1 mm 10…150 Hz)5 cycles not operating
Shock resistance
10 gnin operation
30 gnnot operating